FFY Electric Igniters (Hazardous Area Classification)
August 29, 2017Burner Type
Credfeld Low NOx Air Atomised Burner c/w Venturi and matched flame stabiliser.
Application:
PF Start-up Burners
Fired Fuel
Diesel
Emission Results
| Test | Contract Gaurantee | Credfeld Low NOx Burner Results |
|---|---|---|
| NOx | 320mg/Nm3 @3% O2 vol,dry | 114mg/Nm3 @ 3% O2 vol,dry |
| Dust | 50mg/Nm3 @ 3% O2 vol,dry | 26mg/Nm3 @ 3% O2 vol,dry |