Low NOx Liquid Fuel Burners1) Fire Tube Boilers, Sweden
Credfeld have recently supplied Low NOx heavy oil burners suitable for Fire Tube boilers and meeting the stringent Swedish emissions requirements for liquid fuel fired plant. The burners are equipped with our special split-flame Osynox atomizers. The flame profile is clearly shown in the above photograph. Typical Results:
2) Utility Boiler, Malta
An oil fired power station boiler was fitted with a set of Osynox atomizers to reduce NOx emissions below the European directive of 450 mg/Nm3 from an operating level of around 600 mg/Nm3 without the need to change burner air registers or any other part of the combustion system. This was achieved without compromising boiler load or particulate emissions which were maintained at or below 50 mg/Nm3. Typical Results:
| |||||||||||||||||||||||||||||||||||||||||||||||
| |||||||||||||||||||||||||||||||||||||||||||||||