Low Tension Gas / Electric Ignition with Flame SurveillanceLT300 Ignition Control System

Ignition Control System
The Igniter control system has been designed to offer maximum reliability and flexibility. The Igniter uses only on low tension cable to transmit the spark and also to receive the flame on signal, giving maximum with less congestion of the equipment.

The Igniter Control System provides two functions
  • Spark Generator
  • Flame Monitor

    The Igniter control system is designed to be used in conjunction with a single electrode gas-air mix Igniter rod. The Igniter Coil is mounted at the rear end of the Igniter Rod, and connections are via a 3 way plug and socket. The Igniter coil is fed from a pulsed generator which is switched by a Thyristor. This pulsed supply (140V Half Wave) is applied to the low tension winding of the coil, which in turn, generates the high tension spark.

    Duties:
  • Burner Ignition Systems
  • Permanent Pilot Duties                                                                                                                              

    Signals required from management
  • Spark Signal (24VDC or Volt Free Contact)
  • Command to open Gas/Air Valves (Timed Process)

    During the Spark On period, the ionisation detector rejects any signals from the spark generated, this being taken care of by a capacitor network, thus flame present detection can only take place after the spark is switched off and a flame on signal from the electrode is detected.                                                                                                                                                   

    The Flame On signal is achieved by ionisation. When a gas flame is established, this permits the flow of positive ions between the electrode (Anode) and the Igniter body (Cathode). This gives a variable forward resistance. The Igniter Control System has a set resistance threshold and when this is reached; the relay in the control system is energised, indicated by orange Led Flame On. This change is displayed on a 0-10V analogue signal strength meter, which is incorporated into the unit to indicate when the gas air mix is correct.

  • Specification LT300 Igniter
  • Flame off time response 1 second fixed
  • Flame On output 1 relay changeover contacts rated 240VAC 1 amp
  • Short Circuit Fault Output 1 relay changeover rated 240VAC 1 Amp
  • Operating Temperature 0 - 85C
  • Spark Initiation 24VDC
  • Spark Initiation (Volt Free)
  • Power Requirements 115/230VAC 50/60Hz 20VA +10% -20%
  • 140VDC output to Igniter coil
  • Weight 1.5Kg

    Download the pdf

  •  
    Credfeld Ltd
    Products
    Low NOx Oil & Gas Burners
    PF Light-up Burners
    Single Burner Packages
    Main Flame Monitoring
    LT 300 Gas-Air Igniters
    LT 300 Ignition Control System
    LT 300 Igniton Tester
    Dedicated LT300 Ignition Control System
    LT 300 Igniters
    Modular Valve Systems
    Burner Management Systems
    Services
    Spare Parts
    Case Studies
    About Us
    Site Map
     
    www.intergage.co.uk