Malaysian Newsprint Industries
| No of Boilers |
3 (Three) |
| No of Burners per Boiler |
4 (Four) |
| Burner Positions |
Frontwall |
| Burner Type |
T/Credfeld Low Nox |
| Type of Atomisation |
Steam |
| Firing Rates per Burner |
2304 kg/hr |
| Type of Fuel |
Oil Shell Medium Fuel Oil |
| Oil Pressures |
1200 kPa(g) |
| Atomising Steam Pressure |
600 kPa(g) |
| Burner Turn Down |
6 : 1 |
| Combustion Air Temperature |
230ÂșC |
| Register Size |
445 mm Diameter |
| Excess Air (Design) |
10% |
| Type of Pilot Ignition |
Low Tension Gas/Air Pre-Mix - Model 200 |
| Type of Controls |
DCS - Client Supply |
| Type of Flame Monitoring |
Main Oil Flame - Credfeld System 4 (UV) Pilot Flame - Ionisation |
A single Heating and Pumping Unit was also supplied by Credfeld to meet the fuel oil requirements for all three boilers. In addition Credfeld, following results found during a model study carried out the design of the common combustion air windbox for mounting the 4 oil burners and register |