Malaysian Newsprint Industries

Malaysian Newsprint Industries

No of Boilers   3 (Three)
No of Burners per Boiler  4 (Four)
Burner Positions Frontwall
Burner Type  T/Credfeld Low Nox
Type of Atomisation  Steam
Firing Rates per Burner  2304 kg/hr
Type of Fuel Oil Shell Medium Fuel Oil 
Oil Pressures  1200 kPa(g)
Atomising Steam Pressure 600 kPa(g)
Burner Turn Down 6 : 1
Combustion Air Temperature 230ÂșC
Register Size 445 mm Diameter
Excess Air (Design) 10%
Type of Pilot Ignition Low Tension Gas/Air Pre-Mix - Model 200
Type of Controls DCS - Client Supply
Type of Flame Monitoring

Main Oil Flame - Credfeld System 4 (UV)
Pilot Flame - Ionisation

A single Heating and Pumping Unit was also supplied by Credfeld to meet the fuel oil requirements for all
three boilers. In addition Credfeld,  following results found during  a model study carried out the design
of the common combustion air windbox for mounting the 4 oil burners and register

 