Mumias Sugar Mill - Kenya - Support Burners
| No of Boilers |
1 (One) John Thompson - Bagasse |
| No of Burners per Boiler |
2 (Two) |
| Burner Positions |
Sidewall |
| Burner Type |
Credfeld Fuelburn |
| Type of Atomisation |
Steam |
| Type of Fuel |
Oil HFO - No.6 |
| Firing Rate per Burner |
2800 kg/hr |
| Fuel Oil Pressure |
1200 kPa(g) |
| Atomising Steam Pressure |
600 kPa(g) |
| Burner Turn Down |
6 : 1 |
| Combustion Air Temperature |
100ÂșC |
| Register Draft Loss |
150 mmwg |
| Register Size |
550 mm Diameter |
| Type of Pilot Ignition |
Low Tension Gas/Air Pre-Mix |
| Type of Controls |
Relay Logic |
| Type of Flame Monitoring |
Main Oil Flame - Credfeld System 5 (UV) |
| Pilot Flame |
Ionisation |
Credfeld also designed and supplied the fuel oil Heating & Pumping Unit for the boiler along with the fuel oil and steam system local at the burners. In addition Credfeld carried out the design of the combustion air windbox, which was manufactured in Kenya.
The H & P Unit incorporated both steam and electric inline heaters for oil burner duties. |