| No of Boilers |
3 (Three) 2 Ical & 1 Steinmuller |
| No of Burners per Boiler |
1 Burner on Each Ical Boiler - 4 Steinmuller |
| Burner Positions |
Frontwall |
| Burner Type |
Credfeld Fuelburne Gas/Oil Combination |
| Type of Atomisation |
(Oil) Steam |
| Firing Rates per Burner (Ical) HFO |
3310 kg/hr/Gun - Refinery Gas: 3050 kg/hr |
| Firing Rate per Burner Steinmuller HFO |
2064 kg/hr - Refinery Gas: 2655 Nm³/hr |
| Oil Pressure Supply Max |
900 kPa(g) |
| Gas Pressure Pipeline |
150 kPa(g) |
| Atomising Steam Pressure |
600 kPa(g) |
| Burner Turn Down |
6 : 1 |
| Type of Pilot Ignition |
Low Tension Div1 Gas/Air Pre-Mix Model 200 |
| Type of Controls |
DCS |
| Type of Flame Monitoring |
Main Flames - Credfeld System 4 (UV) |
| Pilot Flame |
Ionisation |